Technical article

Writing Effective Valve Specification Sheets: What Every Engineer Must Include

Expert guide to writing effective valve datasheets covering control valve vs isolation valve data requirements, ISA-S75.22 format, common specification mistakes, and a pre-issue review checklist.

  • A poorly written valve datasheet is a hidden project risk — ambiguous or incomplete specifications lead to technically non-compliant valves, cost-overrun change orders at the last minute, and arguments about scope that could have been avoided with 30 minutes of careful datasheet preparation upfront.
  • ISA-S75.22 and instrument data sheet formats provide a standardised baseline — but the engineering value is in the application-specific information you add beyond the standard fields: service conditions, special inspection requirements, documentation expectations, and any deviations from standard construction.
  • Control valve and isolation valve datasheets serve different purposes and require different information — a control valve datasheet is fundamentally a sizing and performance document; an isolation valve datasheet is a material and pressure rating document; conflating them produces datasheets that serve neither purpose well.

I’ve reviewed enough valve datasheets over the years to know that the quality of the specification document is a strong predictor of how well the procurement process will go. A well-written datasheet gets you competitive bids from qualified suppliers, minimal clarification rounds, and valves that work correctly when they arrive. A poorly written one generates endless RFI responses, substitutions you didn’t intend to approve, and arguments about who’s responsible for the resulting problems. Here’s how to write them properly.

Control Valve Datasheets

A control valve datasheet must contain all information needed to size the valve, specify its construction, and verify its performance. The ISA-S75.22 standard defines a recommended format. Key sections:

Service Conditions (Process Data)

This is the most important section. Include: fluid name and composition (or reference to a stream composition table); fluid state at inlet (liquid, gas, vapour, two-phase); inlet pressure P1 (bar g or psia), minimum/normal/maximum; outlet pressure P2; differential pressure ΔP = P1 – P2; inlet temperature T1; flow rate (kg/h, Nm³/h, US gpm), minimum/normal/maximum; density or specific gravity at operating conditions; viscosity; vapour pressure (for liquids — needed for cavitation check); molecular weight (for gases); specific heat ratio γ (for gases); compressibility factor Z; and inlet and outlet pipe sizes.

Include at least three operating cases: minimum flow (lowest controllable flow, usually at highest P2), normal flow (design flow at normal conditions), and maximum flow (emergency or runaway flow at lowest P2). Some services warrant additional cases (startup, shutdown, turndown).

Construction Specification

Body size and rating (e.g., NPS 4″ Class 300); end connections (ASME B16.5 flanged RF, butt-weld, socket-weld); body material (ASTM grade and specification); trim material (plug, seat ring, cage, stem); packing type and material; bonnet type (standard, extended, bellows seal); flow direction (FTO or FTC — flow to open or flow to close, which defines which end is inlet); seat leakage class (ANSI/FCI 70-2 Class IV, V, or VI); and action (air-to-open or air-to-close, equivalent to fail-open or fail-closed).

Actuator and Positioner

Actuator type (spring-and-diaphragm, piston, electric); fail-safe position (open, closed, last); supply pressure range; positioner type and communication protocol (HART, Profibus PA, Foundation Fieldbus); input signal (4–20 mA, split-range, etc.); and any special requirements (PST capability for ESD service, ATEX rating for hazardous area).

Sizing Results

Required Cv at each operating case; selected Cv (from vendor’s published data at specified travel); actual travel at each case; noise prediction at each case (dB(A)); and cavitation or flashing flag at each case.

Isolation Valve Datasheets

An isolation valve datasheet is simpler than a control valve datasheet because there’s no sizing calculation involved — the valve is either open or closed. But it still needs to specify all parameters that define a compliant valve:

  • Service: fluid, pressure (design and operating), temperature (design and operating), fluid phase
  • Size and rating: NPS/DN, ASME class, end connections
  • Type: ball, gate, globe, butterfly, check — and design variant (full bore, reduced bore, rising stem, etc.)
  • Body material: ASTM grade; special requirements (NACE, low-temperature, cryogenic)
  • Seat/disc material: and seat leakage class if specified
  • Standards: applicable standards (API 600, API 6D, API 609, etc.)
  • Testing: per API 598 as minimum; any additional test requirements (PMI, RT, extended hold time)
  • Documentation: required documentation package (MTR, hydro test certificate, NDE reports)
  • Special requirements: fire-safe (API 6FA), fugitive emissions (API 624/641), anti-static, cryogenic testing
  • Actuation: if actuated — actuator type, fail position, area classification

Common Datasheet Mistakes

Incomplete Process Data

The single most common error: missing or incomplete process data. “Natural gas at 50 bar” is not sufficient to size a valve. Molecular weight? Temperature? Specific gravity? If the process engineer hasn’t provided these, the instrument engineer cannot produce an accurate sizing — and the valve vendor will make assumptions that may not match your actual conditions.

Specifying Only Normal Flow

Sizing a control valve for normal flow only and ignoring minimum and maximum cases produces a valve that either can’t control at low flows (if oversized for minimum) or can’t pass maximum flow when needed. Always specify all three cases.

Leaving Trim Material as “Standard”

“Standard trim” means different things to different manufacturers. Specify the trim material explicitly — 316SS, Stellite-faced, WC HVOF — so you get consistent bids and the right material for your service.

Not Specifying Packing Type

If you’re in a hydrocarbon service requiring fugitive emissions compliance, specify live-loaded graphite packing to ISO 15848 Class B (or A for toxic service). “Standard packing” may get you PTFE braided rings that fail the LDAR inspection in six months.

Omitting Documentation Requirements

Specifying a valve without defining the required documentation package means you’ll chase MTRs, hydrotest certificates, and NDE reports after the fact — often after the valve has been installed and the plant is trying to commission. Define the documentation package on the datasheet.

Copy-Paste from Similar Services Without Review

One of the most dangerous practices. A datasheet from a previous project may have different process conditions, different standards applicability, or different safety requirements. Review every datasheet individually — even if it looks similar to something you’ve done before.

Review Checklist Before Issuing a Datasheet for Inquiry

  • Process data complete: fluid composition, all pressures, all temperatures, all flow cases
  • Vapour pressure included for liquid services (cavitation check)
  • Molecular weight and γ included for gas services
  • Body material confirmed against P-T conditions and service fluid
  • Trim material explicitly specified (not “standard”)
  • Packing type specified with emissions compliance if required
  • Seat leakage class specified
  • Fail-safe position specified and confirmed against safety philosophy
  • Area classification specified for actuated valves
  • Testing standard and any supplementary tests specified
  • Documentation package specified
  • Lead time constraints noted if critical path item

Time invested in quality datasheets is one of the highest-return activities in valve engineering. It protects you from substitutions you didn’t approve, ensures competitive bidding, and dramatically reduces the probability of receiving a valve that doesn’t work for your service.