Industrial control valve installed on a process pipe in a manufacturing facility
  • The inherent flow characteristic of a control valve — linear, equal percentage, or quick opening — describes how flow changes with valve opening in a test rig with constant pressure drop, but in any real process system the pressure drop across the valve changes continuously with flow rate, and the resulting installed characteristic can be dramatically different from the inherent one.
  • Understanding the difference between inherent and installed flow characteristics is the single most important concept in control valve loop tuning — a valve that looks like it has an equal percentage characteristic in the catalogue will behave like a quick-opening valve on a high-drop system and vice versa, causing loops that cannot be tuned correctly regardless of how the PID gains are set.
  • The valve authority — the ratio of pressure drop across the fully open valve to the total system pressure drop — is the parameter that determines how far the installed characteristic deviates from the inherent characteristic, and specifying valves with authority above 0.25 is the practical tool for keeping installed and inherent characteristics reasonably aligned.

Inherent Flow Characteristics Defined

The inherent flow characteristic of a control valve is defined as the relationship between the relative flow coefficient (Cv as a percentage of the maximum Cv) and the valve opening (travel as a percentage of full travel), measured at a constant differential pressure across the valve. This constant-pressure-drop test condition is the definition of the inherent characteristic — it is a property of the valve trim geometry alone, independent of the system in which the valve is installed.

Three inherent characteristics are commonly offered: linear, equal percentage, and quick opening. A linear characteristic produces flow directly proportional to valve opening — at 50 percent travel, the valve passes 50 percent of maximum flow; at 75 percent travel, 75 percent of maximum flow. The trim geometry for a linear characteristic is designed so that each incremental percentage of travel adds the same absolute amount of flow coefficient. A globe valve with a linear characteristic typically uses a plug with a contoured shape that provides equal Cv increments per unit travel.

An equal percentage characteristic produces flow increments that are a constant percentage of the current flow for each percentage of travel increment. At low openings, each increment of travel adds a small absolute amount of flow. At high openings, each increment adds a much larger amount. The ratio of the maximum to minimum controllable Cv — the rangeability — is constant on a logarithmic scale. Equal percentage characteristics are the most widely specified in process control applications because they have better controllability than linear characteristics over wide flow ranges, as will be explained when discussing installed characteristics. The trim geometry for equal percentage produces small flow changes at low openings and large changes at high openings.

Quick-opening characteristics produce most of the maximum flow at small valve openings — the Cv increases rapidly in the first 20 to 30 percent of travel and then levels off. Quick-opening trim is used in applications where the valve needs to provide large flow changes quickly, such as pressure relief bypass applications, emergency flow provisions, and dump valves. It is not suitable for throttling control because even small position changes at low openings produce large uncontrollable flow changes.

Why Installed Characteristics Differ

The installed characteristic is what you get in the real system. In any process system with pumps, pipes, heat exchangers, and other equipment in series or parallel with the control valve, the differential pressure across the valve is not constant — it changes with flow rate. As flow increases through the system, the friction pressure losses in the pipework increase (proportional to velocity squared), and the pressure available to drive flow through the valve decreases correspondingly. This means the valve is operating at higher pressure drop at low flows (when system resistance is low) and lower pressure drop at high flows (when system resistance absorbs most of the available pressure).

The mathematical consequence of this pressure variation is that the installed characteristic — the actual flow versus travel relationship in the real system — is distorted relative to the inherent characteristic. For a valve with an equal percentage inherent characteristic installed in a system where the pressure drop varies significantly with flow, the installed characteristic becomes more linear or even tends toward quick-opening. For a valve with a linear inherent characteristic in the same high-pressure-drop-variation system, the installed characteristic becomes quick-opening. Both distortions are in the same direction (toward quick-opening behaviour) because the physical effect is the same: at high openings where the valve is trying to pass the maximum flow, the reduced differential pressure limits the flow increase per increment of travel, compressing the upper end of the characteristic curve toward quick-opening shape.

Valve Authority: The Key Parameter

Valve authority (alpha or beta in different textbook conventions) quantifies how much the system pressure variation affects the installed characteristic. It is defined as the ratio of the valve pressure drop at fully open conditions to the total system pressure drop at those same fully open conditions. An authority of 1.0 means the valve takes all the system pressure drop at full open — the installed and inherent characteristics are identical. An authority of 0 means the valve takes none of the system pressure drop — the installed characteristic is distorted beyond recognition.

In practice, achieving high valve authority means sizing the valve to have a significant pressure drop even when fully open — deliberately under-sizing the valve, in a sense. A valve sized to have authority of 0.5 at maximum flow will carry half the total system pressure drop when fully open, which is a substantial portion. The system pump or pressure source must provide this additional pressure drop across the valve even at maximum flow. The energy consumption and operating cost of maintaining this excess valve pressure drop is the price paid for good valve authority and well-behaved installed flow characteristics.

The rule of thumb in most control valve engineering texts is to target valve authority above 0.25 (the valve takes at least 25 percent of total system pressure drop at full open) and ideally above 0.5. Below 0.25, the installed characteristic distortion becomes severe enough that equal percentage trim is needed just to compensate for the distortion and achieve approximately linear installed behaviour. Below 0.1, the valve is essentially a pressure-drop-negligible component in a high-resistance system, and no choice of inherent characteristic will produce controllable installed behaviour.

Trim Selection to Compensate for Low Authority

When valve authority cannot be increased (because the system pressure is fixed by the process and cannot be artificially inflated to provide more valve pressure drop), trim selection can partially compensate for the installed characteristic distortion. The principle is that a logarithmic inherent characteristic (equal percentage) tends toward linear when installed in a low-authority system, so specifying equal percentage trim in a system where linear installed behaviour is desired makes physical sense. Conversely, a linear inherent characteristic in a moderate-authority system will produce a slightly quick-opening installed characteristic, and equal percentage trim will give a more linear installed result.

The selection of equal percentage versus linear inherent characteristic as a function of valve authority is one of the oldest and most useful tools in control valve engineering. A simplified version of the rule is: use equal percentage trim for systems with valve authority below 0.5, and linear trim for systems with authority above 0.5. This rule is a simplification — the correct selection also depends on the process gain variation over the flow range and the requirements of the control loop — but it provides a defensible starting point for most applications.

Process Gain and PID Tuning Implications

The installed flow characteristic matters most for loop tuning because it directly determines the process gain — the change in controlled variable per unit change in valve position. For a well-tuned PID loop to maintain stable control across its operating range, the process gain must not vary too much with operating point. If the installed characteristic has a quick-opening shape (large flow changes at small openings, small changes at large openings), the process gain will be very high at low valve positions and very low at high valve positions. A PID tuned for stability at one operating point will either oscillate or respond sluggishly at other points.

Gain scheduling — automatically adjusting the PID gains as a function of valve position or operating point — is used in advanced control applications to compensate for process gain variation. But gain scheduling adds complexity and is only justified when the process gain variation is inherent to the process and cannot be addressed through valve selection and sizing. For most applications, the better solution is to specify the valve correctly in the first place: adequate authority, appropriate inherent characteristic, and correct trim type for the flow range.

Rangeability is the related concept that affects loop performance at the low end of the flow range. Rangeability is the ratio of maximum to minimum controllable flow through the valve — a valve with a rangeability of 50:1 can control flow at rates between 2 percent and 100 percent of maximum. Real control valve rangeability in an installed system is always less than the inherent rangeability quoted by the manufacturer, because the pressure variations in the installed system reduce the minimum controllable flow. In systems with low valve authority, the installed rangeability may be considerably less than half the inherent rangeability — a significant limitation for applications requiring wide flow range control, such as variable-demand heat exchangers or variable-load boiler feedwater systems.

Diagnosing Installed Characteristic Problems in Service

When a control valve loop cannot be tuned — when increasing the controller gain causes oscillation at some operating points while insufficient gain at others — the first diagnosis to investigate is installed characteristic mismatch. A loop that oscillates at low valve position but is sluggish at high position has a quickly-opening installed characteristic: high process gain at low openings (gain too high, oscillation) and low process gain at high openings (gain too low, sluggish). This pattern is diagnostic of a valve operating in a low-authority system with a linear or inappropriate inherent characteristic.

The diagnostic procedure is to plot the actual flow (or the controlled variable response) against valve position across the operating range. If the resulting curve is concave upward (steep slope at low positions, shallow slope at high positions), the installed characteristic is quick-opening and the valve is in a low-authority system. If concave downward (shallow at low positions, steep at high positions), the valve is oversized or the inherent characteristic is equal percentage in a high-authority system — both of which also cause tuning problems but in opposite directions.

The permanent fix for an installed characteristic problem is to resize the valve — either changing the trim (cage, plug, or disc) to a different inherent characteristic, or replacing the valve with one that achieves better authority for the system conditions. Temporary fixes using gain scheduling or adaptive control are legitimate for avoiding a shutdown, but they do not address the root cause and create ongoing maintenance complexity. If the root cause analysis confirms a specification error in the original valve sizing, the correct engineering response is to correct the specification, not to patch the control system indefinitely.

Practical Guidance for Valve Specification

When sizing a control valve, always calculate the valve authority at the normal operating flow point and at the maximum flow point. If the authority is below 0.25 at any operating condition within the normal operating range, the specification must address the installed characteristic either by increasing the system pressure drop budget allocated to the valve, by selecting equal percentage trim, or by accepting reduced rangeability and documenting this in the loop design basis. Do not leave installed characteristic assessment to be discovered during loop tuning.

The valve data sheet should state the selected inherent characteristic, the calculated valve authority at the normal operating point and at the design maximum flow, and the expected installed rangeability. These values are the starting point for the control loop designer’s tuning assessment. A valve specified only by Cv, pressure rating, and body material, with no documentation of the intended inherent characteristic and operating authority, is incompletely specified and will cause predictable but avoidable control problems during commissioning.