Quick summary:
- Inherent flow characteristic (the relationship between valve opening and Cv) determines how the control loop gain changes across the operating range — selecting the wrong characteristic leads to poor control performance at part-load or full-load conditions
- Equal percentage characteristic compensates for the non-linear gain of most process systems (where ΔP across the valve falls as flow increases), producing an installed characteristic that is closer to linear
- Correct characteristic selection requires analysis of the installed pressure drop ratio across the valve relative to total system ΔP — not just matching characteristic names to application types
Why Flow Characteristic Matters to Control Loop Performance
The flow characteristic of a control valve is the relationship between valve opening (expressed as fraction of full travel, 0 to 1) and the valve flow coefficient Cv at that opening, under constant differential pressure. It is called the “inherent” characteristic because it is measured and defined under ideal conditions — specifically, with constant ΔP across the valve throughout the travel range.
In real process systems, differential pressure across the valve is not constant. As flow increases, frictional pressure losses in the piping, heat exchangers, and other equipment increase (proportional to flow squared), leaving less pressure drop available across the valve. This means the actual installed characteristic — the relationship between valve opening and flow in the real system — differs from the inherent characteristic measured in the laboratory.
The reason this matters to control engineers: the process gain of the control loop (how much output variable changes per unit change in controller output) depends directly on how Cv changes with valve opening. If the installed characteristic is highly non-linear — high gain at low openings, low gain at high openings — the controller must be retuned for different operating points, or the loop will be unstable at some conditions and sluggish at others. A well-chosen valve characteristic produces an installed characteristic that is reasonably linear — giving consistent loop gain across the operating range and stable control throughout.
The Three Standard Inherent Characteristics
ISA-75.01 defines three standard inherent flow characteristics, each with a distinct mathematical relationship between opening and Cv:
Linear characteristic: Cv changes in direct proportion to valve opening. At 25% open, Cv = 25% of maximum. At 50% open, Cv = 50% of maximum. At 75% open, Cv = 75% of maximum. The slope dCv/dL is constant across the full travel range. A truly linear installed characteristic is the ideal for control performance — but as we will see, a linear inherent characteristic rarely produces a linear installed characteristic in real systems.
Equal percentage characteristic: Equal increments of valve opening produce equal percentage changes in Cv, not equal absolute changes. The mathematical relationship is Cv = Cvmax × R^(L-1), where R is the rangeability ratio (typically 30-50 for control valves) and L is the fraction of travel from 0 to 1. At low openings, the absolute change in Cv per degree of travel is small. At high openings, the absolute change in Cv per degree of travel is much larger. The gain of the valve increases progressively with opening.
This is counterintuitive until you understand why it is useful: in a typical process system where valve ΔP falls with increasing flow, the decreasing ΔP effect reduces flow gain at high flows. An equal percentage valve, which has increasing Cv gain at high openings, approximately compensates for the system’s decreasing ΔP at high flows. The two effects partially cancel, producing an installed characteristic that is approximately linear — which is what we want.
Quick-opening characteristic: Maximum change in Cv per unit travel occurs at small openings, and Cv approaches maximum before the valve reaches full travel. Flow is nearly at maximum at 50% valve opening. Quick-opening is the inherent characteristic of most butterfly valves and ball valves (though these are heavily influenced by actuator and plug geometry). Quick-opening valves are used for on/off service where rapid full flow is needed — not for throttling control.
The Installed Characteristic — What Actually Happens in the Process
The installed characteristic is calculated from the inherent characteristic by accounting for how the valve pressure drop varies with flow in the actual system. The key parameter is the pressure drop ratio β (sometimes called the valve authority):
β = ΔPv,max / ΔPsystem
Where ΔPv,max is the valve pressure drop at maximum flow (when the valve is fully open) and ΔPsystem is the total pressure drop across the system (pipe, equipment, and valve combined) at maximum flow. β ranges from 0 (valve takes negligible pressure drop relative to system) to 1 (valve takes all system pressure drop).
At β = 1 (constant pressure across the valve), installed characteristic = inherent characteristic. This is the laboratory test condition.
As β decreases below 1 (typical process plant conditions where β = 0.2 to 0.5), the installed characteristic of a linear valve distorts toward quick-opening — giving too much flow gain at low openings and too little at high openings. The installed characteristic of an equal percentage valve, however, distorts toward linear — which is why equal percentage is preferred for most control applications.
The crossover point: When β is high (above 0.7), a linear valve may produce a better installed characteristic than equal percentage. This occurs in systems where the valve takes a large fraction of system pressure drop — for example, a pressure-reducing valve station where the valve ΔP dominates the system. In this case, an equal percentage valve’s installed characteristic distorts toward a characteristic with too-high gain at high openings, causing potential instability. A linear valve is preferred here.
Practical Selection Guidelines
These are the rules of thumb used by experienced control valve engineers. They are not absolute — a full installed characteristic analysis should be performed for critical applications — but they provide reliable guidance for the majority of cases:
Use equal percentage when: The valve pressure drop is a small fraction of total system pressure drop (β < 0.5). This is the most common situation in most process plant applications — pump systems, heat exchanger temperature control, distillation column flow control. Equal percentage compensates for the system's natural non-linearity. Also use equal percentage for gas pressure control (where Cv/flow relationships are inherently non-linear due to density changes) and for liquid level control where the relationship between flow and level is non-linear.
Use linear when: The valve takes a large fraction of system pressure drop (β > 0.7). Pressure-reducing valve stations, desuperheating control valves in steam systems with fixed upstream and downstream pressure, and flow control in systems with negligible pipe friction relative to valve ΔP. Also use linear for slurry and non-Newtonian fluid service where the characterisation plug profile of an equal percentage valve is prone to fouling in the narrow trim clearances at low openings.
Avoid quick-opening for control: Reserve quick-opening for on/off service. A quick-opening valve used in a control loop will be saturated at full flow with the valve at only 50-60% travel, leaving no control authority for the upper half of valve stroke.
Rangeability and Turndown — How They Affect Characteristic Selection
Rangeability is the ratio of maximum controllable Cv to minimum controllable Cv for a given valve at constant ΔP. A valve with Cv max of 100 and minimum controllable Cv of 2 has a rangeability of 50:1. This defines the useful operating range of the valve — below minimum Cv, the flow becomes uncontrollable (the valve is effectively closed); above maximum Cv, the valve is wide open and has no control authority.
Equal percentage valves inherently have better rangeability than linear valves of the same Cv max, because the mathematical relationship compresses small Cv values into the low-opening portion of travel. A typical cage-guided globe control valve achieves rangeability of 30:1 to 50:1 with equal percentage trim, compared to 10:1 to 20:1 with linear trim. For applications with large flow turndown requirements — such as once-through boiler feed water control that must operate from 5% to 100% of MCR — this difference is significant.
Installed rangeability is always less than inherent rangeability, because the falling valve ΔP at high flows reduces the available Cv at maximum flow and increases the minimum controllable flow. For systems with β = 0.25, installed rangeability is approximately half the inherent rangeability. This must be factored into valve sizing — a 50:1 inherent rangeability valve may deliver only 25:1 installed rangeability in a typical piped system.
Rotary Valve Characteristics — Ball and Butterfly Valves
Rotary valves (ball valves, butterfly valves, eccentric plug valves) have inherent flow characteristics determined primarily by their plug or disc geometry. Standard ball valves (spherical bore) have an inherently quick-opening characteristic. Standard butterfly valve discs have a characteristic that is approximately quick-opening in the low-opening range and approximately linear in the mid-range.
Characterised ball valve trims — V-port balls, profiled balls — can produce an equal percentage characteristic over a significant portion of the travel range. These are widely used in pulp and paper, food processing, and general chemical plant control where a ball valve is preferred for its full-bore flow path and cleanability, but equal percentage characteristics are required for good control performance.
Segmented ball valves (V-ball, characterized ball) provide equal percentage characteristics with significantly better rangeability than standard ball valves — typically 100:1 or better, compared to 10:1 for a standard ball. The V-shaped port controls minimum flow more precisely than a circular bore ball, which allows very small flow openings without full shutoff.
Installed Characteristic Verification — Simulation and Testing
For critical control loops — reactor feed control, distillation column reflux, heat exchanger bypass temperature control — a formal installed characteristic analysis should be performed during the design phase. This requires the following information: valve Cv versus position data from the manufacturer, system pressure drop versus flow data from hydraulic analysis, and the defined operating range (minimum to maximum flow).
Modern control valve sizing software (Fisher’s ValveLink, Emerson’s AMS Valve Link, Metso’s Nelprof) performs installed characteristic calculations as standard output. The installed characteristic curve should be reviewed for: linearity across the required operating range, adequate rangeability, and absence of inflection points that would cause controller instability at specific operating conditions.
Where the installed characteristic analysis reveals poor characteristics with the initial valve selection, corrective options include: changing valve type (linear to equal percentage or vice versa), installing a smaller valve if the current selection is oversized (oversizing forces the valve to operate at very low openings where characteristics are least linear and controllable), or adjusting the system hydraulics to increase valve pressure drop ratio β.
Characteristic selection is one of those valve engineering details that is easy to overlook in the pressure of project execution and easy to dismiss as theoretical. It is neither. A mismatched characteristic is responsible for countless control loops that perform poorly throughout their service life — loops that maintenance engineers spend years re-tuning without recognising the fundamental cause. Get the characteristic right at the specification stage and you remove one of the most common sources of chronic poor control performance from your plant.